(03)Article · Scheduling

Schedules and calendars:
the last setting
nobody touches

Published 28.09.2026Reading 7 minTopic Scheduling

The time schedule is the only function in a building management system that lowers consumption without installing anything. It is also the one that drifts fastest — and the only one whose drift never raises an alarm.

The figure

A 6,000 m² office building in Valais. Actual occupancy: 47 hours a week. Ventilation running: 168. The schedule did say 06:00–18:00, and it was correct: three years earlier a technician had forced the air handling unit to run permanently for a handover inspection.

One hundred and sixty-eight hours

A week has 168 hours. An office building is occupied for between 45 and 55 of them. A school, around 35 outside the holidays. A municipal sports hall, between 25 and 60 depending on the local clubs. In every case the majority of calendar time is unoccupied time — and it is the schedule, and the schedule alone, that decides what runs during it.

No other control function has this ratio between cost and effect. Optimising a heating curve takes readings and weeks of steps. Replacing a fan takes an order, a shutdown and a budget. Correcting a schedule takes twenty minutes in front of a supervision screen.

That is precisely what makes it invisible. An item with no cost has no budget line, no purchase order and no handover — therefore no owner.

What you find when you open the schedules

The findings repeat themselves from one building to the next.

None of these seven points raises an alarm. On the supervision screen, everything is green. A device forced to run is not in fault: it is doing exactly what it was asked to do.

What the standards say

Time control is not a comfort setting: it is an automation function, assessed as such. The Swiss standard SIA 386.110 — which adopts the method of the European standard EN ISO 52120-1 — classifies installations from A to D according to the automation functions actually present and active. Scheduling of emission, distribution and ventilation, together with occupancy-based control, are among the functions that directly determine that class.

The important word is active. A function present in the controller but never configured, or neutralised by a manual command, produces no effect at all. An installation can therefore be designed as class B and operated as class C or D without a single document saying so. That is the most common situation.

On the protocol side the vocabulary exists and is standardised. BACnet (ANSI/ASHRAE 135) defines dedicated objects — Schedule for the weekly programme, Calendar for exception days — and a sixteen-level priority array on every commandable output, where manual and automatic commands do not occupy the same rank. That mechanism is exactly what distinguishes a temporary override from a permanent manual command. It is available in almost every installation, and used in very few.

Setting up a hierarchy

Three levels are enough, provided they are written into the specification and verified at handover.

The provision that changes everything

An alarm on the duration of a manual command is the only measure that turns a forgotten override into an event somebody deals with. Without it, the hierarchy stays an intention written in a specification.

The audit method

  1. Export every schedule and every calendar, circuit by circuit. Most systems produce a single file; failing that, screenshots will do.
  2. List the forced points, at all priorities. This is the first operation, and often the one that explains everything.
  3. Tie each schedule to a real use and to a person who knows it. Orphan schedules are dealt with last, never first.
  4. Compare with actual occupancy hours, not declared ones. Access-control records, people counting or simply the trend of a CO₂ sensor settle the question within a week.
  5. Check the clock and its synchronisation on every controller, including third-party equipment connected through a gateway.
  6. Reprogramme, then write the annual calendar review into the operating contract. Without that last line, the same audit will be repeated identically in three years.

The table to reuse

This table is annexed to the specification and filled in with the operator. It then becomes the reference document for handover, and afterwards for the annual review.

Circuit / plantArea servedActual occupancyScheduleException daysOptimum startOverride allowedOwner
AHU 01Offices, levels 1–2Mon–Fri 07:00–18:00Mon–Fri 06:30–18:30Valais holiday calendarYesOperator, 4 h maxProperty manager
Heating circuit 1Offices, levels 1–2sameMon–Fri, setback 19:00–05:00Valais holiday calendarYesOperator, 24 h maxProperty manager
AHU 02Multi-purpose hallOn bookingOutside schedule, on request—NoOn bookingMunicipality
Heating circuit 3To be identifiedUnknownContinuousNoneNo——
Scheduling table to annex to the specification

The last row is the one that matters. A circuit with no identified use runs continuously because nobody dares stop it. Naming it in a signed table is what finally triggers the investigation.

What it changes

The order of magnitude deserves an honest statement: correcting schedules does not refurbish a building. On an installation whose schedules have drifted, the reduction applies to the running hours of the auxiliaries and to unnecessary warm-up periods — a real, measurable saving, obtained without investment.

But the main gain lies elsewhere. A building in which every circuit has an identified use, a justified schedule and a named owner is a building that can be tuned. Until that table exists, every subsequent optimisation — heating curve, variable flow, free cooling — will apply to an installation that runs, in any case, three times longer than it needs to.

wall-i is an independent engineering office for BMS and building automation, based in Valais, Switzerland. Our specifications are open to every brand and our deliverables follow the SIA standards and the KBOB naming convention. A subject you would like us to cover: hello@wall-i.ch

Contact

A subject you would like us to cover?

Write to us hello@wall-i.ch We get back to you quickly.
Follow on LinkedIn